When spacing for MVHR ducts is tight, a combined intake-exhaust grille may be the solution

Building Regulations requires that an MVHR’s intake grille (bringing fresh air into the property) and the MVHR’s exhaust grille (exhausting air from the property) should be 1.5 metres apart from each other. This is to prevent the system from sucking in the warm, humid exhaust air back into the property, also known as “cross-contamination”.

The MVHR intake supply grille should also be two metres from the boiler flue, and far from the chimney, etc. It should also be at least 300mm from any windows – although noise from an MVHR isn’t normally significant given the very low airflow rates.

When space limitations cannot allow for a 1.5 metre gap between the MVHR intake and exhaust grille (especially in smaller properties), it is possible to use a specially-made combined intake-exhaust grille, such as a MAICO KWH, pictured:

MAICO KWH Combined Intake-Exhaust grille for MVHR systems

This diverts warm air up and away from the property, and allows cold supply air to be fed into the MVHR from below, preventing any possibility of cross-contamination of air supplies.

That means fresh, filtered cold air into the home, in a neat and tidy external grille that’s weatherproof and easy to clean.

Patrick

2 Comments

  1. Really interesting intake/exhaust solution, I was curious about which Building regulation the 1.5m separation comes from? As I’ve come across a 2m figure previously.

    • Hi John,

      Where did you come across the 2m figure? I will revise the post accordingly if it’s wrong.

      From what I’ve researched, Building Regulations states:

      “It is recommended that the supply and extract air terminals are separated by a minimum of 300mm horizontally if placed on the same fa├žade of a building.”

      There is also a distance requirement for MVHR system outlets from boiler flues and other exhaust grilles:

      “To prevent cross-contamination, intake ductwork terminals should normally be separated from exhaust ductwork terminals and other potential sources of pollution by a minimum of 1m measured on plan. Increased separation distances may be required between the intake and any soil and vent pipe terminal, boiler flue outlet or biomass or solid fuel chimney terminal.”

      Our guidance is normally 1 – 2m from any other element if possible – window, boiler flue, bin store, eaves, etc – but as with all guidance we weight it up on a bespoke project basis.

      Do you have a project you’re designing currently?

Leave a Reply

Your email address will not be published. Required fields are marked *